Air | water heat pumps
WPL 24 A – Technical Data

  • Type

    Product Number

    236413

    Output at A2/W35 (EN 14511)

    9,04 kW

    Output at A-7/W35 (EN 14511)

    13,45 kW

    Coefficient of performance at A-7/W35 (EN 14511)

    3

    Coefficient of performance at A2/W35 (EN 14511)

    4

    Technical data

    Energy efficiency class, heat pump W35

    A+++

    Energy efficiency class, W55 heat pump

    A++

    Energy efficiency class, composite system (heat pump + controller) W35

    A+++

    Energy efficiency class, composite system (heat pump + controller) W55

    A++

    SCOP (EN 14825)

    4,58

    Sound power level (EN 12102)

    59 dB(A)

    Sound pressure level at 5 m distance in a free field

    37 dB(A)

    Rated compressor voltage

    400 V

    Rated voltage, emergency/booster heater

    400 V

    Max. application limit on the heating side

    65 °C

    Colour

    white

    Height

    1434 mm

    Width

    1240 mm

    Depth

    1280 mm

    Weight (standard appliance)

    201 kg

    Total weight - external installation

    279 kg

    Technical data and product variants

    For further details and product variants please refer to data sheet.